GGD Series


Generator Gas Dryer
Flow Rate: 8 - 12 ACFM, Hydrogen
Max Pressure: 100 psi
Models: GGD II
Manufacturer: E/One

Water, oil, and other contaminants cause corrosion in critical areas of electric power generators, resulting in diminished efficiency and increasing the likelihood of forced outages. Increased dew point levels also detract from generator efficiency by increasing windage losses. E/One's Generator Gas Dryer (GGD II) is a dual-chamber system that continuously dries and recirculates generator cooling gas — even when the generator is on turning gear, which is a critical time to maintain low dew point.

Column regeneration is automated and takes place based on programmable inlet and outlet dew point levels. The GGD II has a secondary, programmable, time-based regeneration feature, allowing you to set maximum times between regeneration (from 10 to 30 days).

Features & Benefits

  • Increased generator efficiency and reduced downtime
  • Comprehensive water and contaminant removal
  • Microprocessor controlled
  • Flameproof, explosion-proof, and intrinsically safe design
  • Self-monitored drying process
  • Standard electrical actuator, or optional pneumatic
  • Two-wire, Modbus communications (RS 232/485, 9600 Baud) available
  • Compact design great for retrofits (83" H x 27" W x 38" D)

E/One products are only available in Southern counties of NY and Northern counties of NJ only.